Key Takeaways
- Per unit is a change of scale, and students hold onto it once they can read values back into volts, amps and ohms.
- Base selection has two free choices, base power and one base voltage, and transformer ratios set everything after that.
- Showing one feeder in actual units and in per unit lets students check their own bases and explain any mismatch.
Students stop guessing base values once they see the per unit system as a change of scale applied to a network they already understand.
Most courses introduce per unit as arithmetic. You pick a base power, pick a base voltage and divide. Students get good at the division and still freeze when a setting sheet lists a transformer at 0.08 per unit. About 16,300 openings for electrical and electronics engineers are projected each year in the United States, and graduates who move into power roles will read studies, nameplates and settings written in per unit.
The fix is to teach normalization as something you can watch. Build one feeder in simulation software, read it in volts and amps, then read it again in per unit. Base values stop being a memorized recipe when students see every quantity rescale against them. Add worked examples from that single network, and the arithmetic finally has something to describe.
What the per unit system means in power systems
The per unit system expresses every voltage, current, power and impedance as a fraction of a chosen base quantity. A value of 1.0 per unit equals the base, so 0.95 per unit voltage on a 12.47 kV feeder is 11.85 kV. The physics stays put and only the scale moves.
A mark of 42 means little until you know the exam was out of 50, and per unit carries that denominator with it. A bus sitting at 1.03 per unit is 3% above nominal on a 480 V panel and on a 230 kV line alike. That’s why a load flow report can list hundreds of buses in one column and stay readable. Ask a class what 1.0 per unit current means on their feeder, and you’ll learn who has the idea and who only has the procedure.
How per unit values are calculated from base quantities
A per unit value is the actual quantity divided by its base quantity in the same units. You choose two bases, normally three-phase apparent power and line-to-line voltage, and derive the rest. Base current is base power divided by the square root of 3 times base voltage. Base impedance is base voltage squared divided by base power.
Take a 12.47 kV feeder on a 10 MVA base. Base impedance works out to 12.47 squared divided by 10, or 15.55 ohms, and base current is 463 A. A line section with 1.24 ohms of series impedance becomes 0.08 per unit, and a load drawing 232 A is drawing 0.5 per unit current. Every per unit system calculation repeats those two steps.
Choosing base values for a network with several voltage levels
Choose one base power for the whole network and one base voltage for each voltage zone, with the zones tied by transformer nominal ratios. Base power is usually a round figure such as 10 MVA or 100 MVA.
A feeder fed from a 69 kV source through a 69/12.47 kV substation transformer has two zones. Set 10 MVA across both, with 69 kV upstream and 12.47 kV downstream. Students guess here because they see three free choices where there are really two. Once base power and one base voltage are fixed, the transformer ratio sets the other, and the base currents and impedances follow.
Equipment rarely arrives on your chosen base. A 2.5 MVA service transformer labelled 6% is quoted on its own rating, so on the 10 MVA system base it becomes 0.24 per unit. Skipping that conversion gives answers that look plausible and are wrong by a factor of 4, so it’s worth setting a problem that exposes it.
“Students guess here because they see three free choices where there are really two.”
Why power system analysis relies on per unit quantities
Power system analysis uses per unit because it removes voltage level from the comparison. Quantities on both sides of a transformer line up, equipment of very different sizes falls into familiar ranges, and errors stand out. The advantages of per unit system notation show up in every study you’ll run.
Five matter most when you’re teaching the method.
- Voltages read directly against nominal, so 0.92 per unit signals a problem at any voltage level.
- Transformer impedances match on either winding, which removes turns ratio bookkeeping.
- Machine and transformer impedances sit within typical ranges that make data entry mistakes easy to spot.
- The square root of 3 drops out of balanced three-phase relationships.
- Results from networks of different sizes can be compared on a common scale.
Students undervalue the third point. An engineer checking a voltage stability study doesn’t recompute every bus. They scan for values outside the expected range, and per unit makes that scan possible.
How per unit simplifies transformer calculations across a feeder
Per unit simplifies transformer calculations because a transformer’s impedance has the same per unit value on both windings when the base voltages follow its ratio. The ideal turns ratio disappears from the circuit, and the transformer becomes a single series impedance.
The 10 MVA, 69/12.47 kV unit at 8% shows it. Base impedance is 476.1 ohms on the high side and 15.55 ohms on the low side, so 0.08 per unit is 38.1 ohms seen from 69 kV and 1.24 ohms seen from 12.47 kV. In per unit, there’s one number and no side to track.
The United States has 60 million to 80 million distribution transformer units in service, and nameplate impedance is conventionally stated in percent on the unit’s own rating. That percentage is a per unit value multiplied by 100. A student who can move it to a system base can place a unit into a feeder study without touching a turns ratio.
Reading a 0.08 per unit impedance during a fault
A 0.08 per unit impedance means rated current through the equipment drops 8% of rated voltage across it. Turn that around for a fault. With full voltage behind it and a bolted three-phase fault on the far side, the current is 1 divided by 0.08, or 12.5 times rated current.
On the 10 MVA transformer feeding the 12.47 kV bus, 12.5 per unit is about 5,790 A against a 463 A base. Students who can produce 0.08 on paper often can’t say that out loud. They’ve computed a ratio and never connected it to the breaker that has to interrupt the current.
This reading makes fault analysis intuitive. Low per unit impedance means a stiff supply and high fault duty. High per unit impedance means more voltage drop under load and less current to clear. Source impedance adds in series, so the actual figure will be lower.
Modelling one feeder in actual units and per unit

Modelling the same feeder twice, once in volts and amps and once in per unit, turns normalization into something students can observe. Only the display moves, so every difference between the two views traces back to the base values.
SPS SOFTWARE lets a class switch the same network between actual units and per unit with a single toggle. Fault the 12.47 kV bus and read about 5,790 A. Flip the toggle and the same measurement reads 12.5 per unit. Nobody recalculated anything. Students see their hand-computed bases confirmed by a model they can inspect, and a wrong base shows up as a mismatch they have to explain.
| What students look at | Read in volts, amps and ohms | Read in per unit |
| Bus voltage under load | 11.85 kV needs the nominal value beside it. | 0.95 reads as 5% low on sight. |
| Substation transformer impedance | 38.1 ohms or 1.24 ohms depending on the winding. | 0.08 applies on either winding. |
| Fault current at the bus | About 5,790 A needs the equipment rating for context. | 12.5 is the multiple of rated current. |
| A base chosen in error | Nothing moves, since physical values ignore the base. | Every value shifts and the mistake becomes visible. |
| Two feeders of different size | Figures scale with rating and resist ranking. | Values from both feeders sit on one scale. |
“An engineer who sees 0.08 per unit and thinks of voltage drop, fault duty and equipment rating in the same breath will catch mistakes that a calculator won’t.”
Teaching per unit as a way of seeing the network
Per unit sticks when students treat it as a lens on a network they already know, and that takes more than a formula sheet. Teach the basics, then make students read values back into volts, amps and ohms until the move is automatic. The arithmetic was never the hard part.
A model adds repetition without redrawing the circuit. Adjust the base power, and the class watches every per unit value move while the physical feeder holds still. That back and forth builds judgment. It fits into a lab curriculum without displacing the hand calculations that come first.
The habit you’re building lasts. An engineer who sees 0.08 per unit and thinks of voltage drop, fault duty and equipment rating in the same breath will catch mistakes that a calculator won’t. It takes one feeder, two views and enough practice that guessing stops. Eligible students can get SPS SOFTWARE for coursework through a sponsoring professor under its educational offer.